CDV6
◼Monitor its own operating voltage (true RMS measurement),
45Hz~65Hz wide frequency measurement.
◼Two sets of output contacts are used for protection and fault
alarm.
◼8 kinds of rated voltages are adjustable, suitable for voltages in
various regions of the world.
◼3-phase 3-wire and 3-phase 4-wire specifications are optional.
◼The voltage measurement accuracy is ≤1%.
◼Anti-harmonic design, optimized for high anti-interference
occasions.
◼The working status of the relay is indicated by an LED indicator.
◼Ultra-small size, only 18mm width, 35mm card rail installation.
Application
◼Used for equipment protection and control (tower cranes, air
conditioners, elevators, agricultural equipment, refrigerated
trucks).
◼Protect the equipment to prevent accidents caused by reverse
operation.
◼Normal/emergency power switch.
◼Prevent phase disconnection of the power load.
No |
tem |
Code |
Description |
||
① |
Product name |
CDV6 |
Voltage monitoring relay |
||
② |
Fonction code |
|
Overvoltage/undervoltage is selected by knob |
||
2 |
It also has over and under voltage function |
||||
③ |
Output contact |
10 |
Output contact 10A |
||
16 |
Output contact 16A |
||||
④ |
Rated operating voltage |
Code name |
Rated supply voltage |
Limit operating voltage |
Set voltage range |
D12 |
DC12V |
DC 7..20V |
DC 9..15V |
||
AD48 |
AC/DC 24..48V |
AC/DC 15…270V |
AC/DC 20.80V |
||
AD240 |
AC/DC 110.…240V |
AC/DC 50.…270V |
AC/DC 65.…260V |
||
A220 |
AC 220V |
AC 160...270V |
AC 180…260V |
CDV6-01 |
CDV6-02 |
||
Function |
Voltage monitoring |
||
Power terminal (monitoring terminall |
A1(+)-A2(-) |
||
Rated supply voltage |
DC12V,AC/DC24V-48V,AC/DC110V-240V,AC220V |
||
Rated power frequency |
45Hz-65Hz,0 |
||
Rated insulation voltage |
460V |
||
Hysteresis value |
5%-20% |
3%fixed |
|
Power indicator |
Green LED |
||
Action delay time |
0.1s-10s,10% |
||
Voltage measurement error |
≤1% |
||
Power-on delay time |
0.5s |
||
Knob setting accuracy |
10% |
||
Recet time |
1s |
||
Temperature fluctuation error |
0.05%/℃,at=20℃ |
||
Output contact Parametare |
10A |
1*10A 250VAC/24VDC |
2*10A 250VAC/24VDC |
16A |
1*16A 250VAC/24VDC |
2*16A 250VAC/24VDC |
|
Minimum switching power |
500mW |
||
Output relay indication |
Red LED |
||
Mechanical life |
1×10⁷ |
||
Electrical life (resistive load) |
1×10⁵ |
||
Operating ambient temperature |
20℃ ~+55℃ |
||
Storage and transportation ambient ten ature |
-35℃ ~+75℃ |
||
nstallation method |
35mm card rail installation |
||
Protection level |
IP20 |
||
Installation location |
Arbitrary |
||
nstallation altitude |
≤2000m |
||
Pollution level |
2 |
||
Wiring ability |
1×2.5mm²or 2×1.5mm²0.8N-m |
||
Dimensions |
90mm×18mm×65mm |
||
Weight |
67g |
Wiring diagram
Panel diagram
Function diagram