Products

CDV6 Three-Phase Voltage Monitoring Relay

As a specialist of CDV6 Three-Phase Voltage Monitoring Relay, CNTD Electric Technology Co., Ltd. can offer you comprehensive selections of goods in this industry.

market@cntd.com

Tel: 18857728107

Whatsapp: 8618857728107

description1
Zipper closure 1/5 zip athletic pullovers for men. Stretchy, lightweight, fast-drying fabric for superior performance. REGULAR FIT - US standard sizes. An athletic fit that sits close to the body for a wide range of motion, designed for optimal performance and all day comfort. FEATURES - Quarter zip closure;Thumbholes on long sleeves to keep them in place during workout
FEATURES

Monitor its own operating voltage (true RMS measurement),

45Hz~65Hz wide frequency measurement.

8 kinds of rated voltages are adjustable, suitable for voltages in

various regions of the world.

3-phase 3-wire and 3-phase 4-wire specifications are optional.

The voltage measurement accuracy is ≤1%.

It has an anti-harmonic model, which is optimized for high anti

interference occasions.

The working status of the relay is indicated by an LED indicator.

Ultra-small size, only 18mm width, 35mm card rail installation.

Application

Used  for  equipment  protection  and  control  (tower  cranes,air conditioners,elevators,agricultural  equipment,refrigerated  trucks).

Protect the equipment to prevent accidents caused by reverse operation.

Normal/emergency  power  switch.

Prevent phase disconnection of the power load.

No

tem

Code

Description

Product name

CDV6

Voltage monitoring relay

 

 

 

 

 

 

 

 

Function code

Eunction code

Overvoltage

Undervoltage

Voltage imbalanc

Action delay

Phase sequence protection

Phase-off

protection

3

 -

 -

 -

 -

 ·

 ·

4

2%...20%

-20%...2%

 -

0.1s.…10s

·

·

5

2%.20%

-20%...2%

8%

0.1s.10s

·

·

6

2%...20%

-20%…2%

5%…15%

2s

·

·

7

 

 

5%.15%

0.1s.…10s

·

·

8

15%

-15%

8%

2s

·

·

Output contact

16

Output contact 16A

Form

None

Common type

X

Anti-harmonic type

 

 

Rated operating voltage

Code name

Rated yoltage gear

P

220-230-240-380-400-415-440-460VAC(P-P)

N

127-132-138-220-230-240-254-265VAC(P-N)

SPECIFIFICATIONS

P

N

Function

Monitor L-L voltage (3-phase 3-wire system)

Monitor L-N voltage(3-phase 4-wire system)

Monitoring termina

L1-L2-L3

L1-L2-L3-N

Power supply

L1-L2

L1-N

Rated operating voltage selection

220-230-240-380-400

415-440-460(P-P)

127-132-138-220-230

-240-254-265(P-N)

Measuring frequency range

45Hz-65Hz

Measuring range

76V-552V

101V-318V

Voltage threshold range

2%-20%(rated voltage)

Unbalanced value threshold range

5%-15%

Voltage fixed hysteresis rate

2%

Power indicator

Green LED

Action delay time

0.1s -10s(Adjustable)

Voltage measurement erro

≤1%

Power-on delay time

0.5s

Knob setting accuracy

10%

Reset time

1s

Temperature fluctuation error

0.05%/℃,at=20℃

Output contact

parameters

16A

2*16A 250VAC/24VDC

Minimum switching powe

500mW

Output relay indication

Red LED

Mechanical life

1×10⁷

Electrical life(resistive load)

1×10⁵

Uperating ambient temperature

-20℃ ~+55℃

Storage and transportation ambient ten    L][

-35℃~+75℃

Installation method

35mm card rail installation

Protection level

IP20

Installation location

Arbitran

Installation altitude

≤2000m

Pollution level

2

Wiring ability

1×2.5mm²or   2×1.5mm²0.8N·m

Dimensions

90mm×18mm×65mm

Weight

67g

CONTROL OUTPUT DIAGRAM

Wiring diagram

Panel diagram

Function diagramw

A powerful company

  •  NO. 258. Wei Eleven Road, Yueqing Economic Development                   Zone, Yueqing City, Zhejiang Province,P.R. China
  •  +86 18857728107

CONTACT US

Copyright © 2020 Singoo