CDV6 Three-Phase Voltage Monitoring Relay (2 Sets Of Outputs)

◼Monitor its own operating voltage (true RMS measurement),
45Hz~65Hz wide frequency measurement.
◼Two sets of output contacts are used for protection and fault
alarm.
◼8 kinds of rated voltages are adjustable, suitable for voltages in
various regions of the world.
◼3-phase 3-wire and 3-phase 4-wire specifications are optional.
◼The voltage measurement accuracy is ≤1%.
◼Anti-harmonic design, optimized for high anti-interference
occasions.
◼The working status of the relay is indicated by an LED indicator.
◼Ultra-small size, only 18mm width, 35mm card rail installation.
Application
◼Used for equipment protection and control (tower cranes, air
conditioners, elevators, agricultural equipment, refrigerated
trucks).
◼Protect the equipment to prevent accidents caused by reverse
operation.
◼Normal/emergency power switch.
◼Prevent phase disconnection of the power load.
No |
tem |
Code |
Description |
|||||
① |
Product name |
CDV6 |
Voltage monitoring relay |
|||||
② |
Function code |
Functior code |
Overvoltage |
Undervoltage |
Voltage imbalance |
Action delay |
Phase sequence protection |
Phase-off protection |
3D |
- |
- |
- |
- |
* |
* |
||
4D |
2%...20% |
-20%...2% |
|
0.1s…10s |
* |
* |
||
5D |
2%...20% |
20%....2% |
8% |
0.1s...10s |
* |
* |
||
6D |
2%…20% |
-20%.2% |
5%.15% |
2s |
* |
* |
||
7D |
|
|
5%….15% |
0.1s…10s |
* |
* |
||
8D |
15% |
-15% |
8% |
2s |
* |
* |
||
③ |
Output contact |
08 |
Output contact 8A |
|||||
④ |
Form |
None |
Common type |
|||||
X |
Anti-harmonic type |
|||||||
⑤ |
Rated operating voltage |
Code name |
Rated voltage gear |
|||||
P |
220-230-240-380-400-415-440-460VAC(P-P) |
|||||||
N |
127-132-138-220-230-240-254-265VAC(P-N) |
P |
N |
||
Function |
Monitor L-L voltage (3-phase 3-wire system) |
Monitor L-N voltage (3-phase 4-wire system) |
|
Monitoring terminal |
L1-L2-L3 |
L1-L2-L3-N |
|
Power supply |
L1-L2 |
L1-N |
|
Rated operating voltage selection |
220-230-240-380-400 415-440-460(P-P) |
27-132-138-220-230 -240-254-265(P-N |
|
Measuring frequency range |
45Hz-65Hz |
||
Measuring range |
76V-552V |
101V-318V |
|
Voltage threshold range |
2%-20%(rated voltage) |
||
Uobalanced value threshold range |
5%-15% |
||
Voltage fixed hysteresis rate |
2% |
||
Power indicator |
Green LED |
||
Action delay time |
0.1s -10s(Adjustable) |
||
Voltage measurement error |
≤1% |
||
Power-on delay time |
0.5s |
||
Knob setting accuracy |
10% |
||
Reset time |
1s |
||
Temperature fluctuation error |
0.05%/℃,at=20℃ |
||
Output contact parameters |
8A |
2*8A 250VAC/24VDC |
|
Minimum switching power |
500mW |
||
Output relay indication |
Red LED |
||
Mechanical life |
1×10′ |
||
Electrical life (resistive load) |
1×10⁵ |
||
Operating ambient temperature |
-20℃ ~+55℃ |
||
Storage and transportation ambient re |
-35℃~+75℃ |
||
nstallation method |
35mm card rail installation |
||
Protection level |
IP20 |
||
loetallation locatior |
Arbitrary |
||
nstallation altitude |
≤2000m |
||
Pollution level |
2 |
||
Wiring ability |
1×2.5mm²or 2×1.5mm²0.8N-m |
||
Dimensions |
90mm×18mm×65mm |
||
Weight |
67g |
Wiring diagram